Специализированные производители контрольно - измерительных приборов
Национальная & quot; горячая линия & quot;:+86 021-64208466
Продукты

Building Materials Monomer Combustion test Dust Removal Equipment

In a monomer combustion test, the material combustion can produce large amounts of smoke and dust, w

Электронная почта: info@standard-groups.com

Содержание

In a monomer combustion test, the material combustion can produce large amounts of smoke and dust, which pollutes the environment. Therefore, a suitable equipment is required to carry out purification treatment. For this reason, our company have taken reference of a variety of forms of dust removal equipment at home and abroad to develop a new generation of dust treatment equipment combined with the actual situation of monomer combustion test together with foreign experts. The equipment can not only effectively reduce the smoke content in the pipeline in order to make the smoke emission in full compliance with national requirements, but also avoid the dust removal equipment to impact the exhaust gas flow rate.
 
image.png
Стандарты
GB/T 20284-2006 Monomer combustion test of building materials and products.
 
Технические параметры

ПроектыПараметры
Air exhaust volume2400 m3/h
Pressure3000 Pa
Filter mediaNon-woven fabric
Endured temperature110℃
Filter cartridge9 pieces
Filtering area45m2
filter cartridge sizeφ200mm×660mm
Inlet dust concentration≤100 g/m3( standard state)
Outlet dust concentration≤30m g/m3( standard state)
Cleaning methodPulsed compression air
Consumption of compressed air0.37 m3/min
PowerAC 380V, three-phase and five-wire system


Характеристики
1. Filter-type automatic cleaning dust collector with polymer anti-high temperature electrostatic coated filter media filter cartridge;
2. With the top vertical installation, the pulse cleaning system blows dust from the top to the internal filter cartridge;
3. Cartridge has a cover flange. The area between the cover flange and the board is sealed by rubber, and fixed with bolt;
4. Cleaning method is time sequential cleaning;
5. Electrical control cabinet uses Siemens PLC control.
6. Configured high-power fan directly controls the volume flow rate of the flue.
 

Вышеуказанный контент предназначен для ссылки и общения только между инсайдерами отрасли и не гарантирует его точности или полноты. Согласно соответствующим законам и нормативным актам и правилам этого веб-сайта, подразделения или лица, приобретающие связанные с ними предметы, должны получить действительную квалификацию и условия квалификации.


Онлайн сообщение

Контактные данные

Телефон компании

+86-21-6420 0566

Время работы

С понедельника по пятницу

Мобильный телефон:

13816217984

Электронная почта:

info@qinsun-lab.com

QR-код